根(gen)據《供熱通(tong)(tong)(tong)風(feng)設(she)(she)計手冊(ce)》規(gui)范(fan)GBJ19-87和(he)《DB42實驗室(shi)通(tong)(tong)(tong)風(feng)系統(tong)設(she)(she)計與施工(gong)規(gui)范(fan)》的(de)相(xiang)關規(gui)定,確定通(tong)(tong)(tong)風(feng)柜(ju)、消(xiao)化(hua)柜(ju)、原(yuan)子吸收罩等通(tong)(tong)(tong)風(feng)設(she)(she)備(bei)、室(shi)內(nei)全(quan)面通(tong)(tong)(tong)風(feng)換氣的(de)通(tong)(tong)(tong)風(feng)量:
1) 設計(ji)中,按室內余熱、余濕、保證室內衛生條件的最小(xiao)換氣量(liang)進行(xing)計(ji)算。
一般(ban)性化(hua)學實驗室的通(tong)風量: 10-12次/小(xiao)時
毒(du)氣室、有機合(he)成、菌種培養的通風量:15-20次/小時
2) 通(tong)風柜(ju)(罩(zhao))排風工作面必須保持負壓狀(zhuang)態(tai),通(tong)風柜(ju)面風速:
VAV狀態(tai) 0.5m/s±0.1m/s或根據(ju)用戶(hu)要求設定(ding)其(qi)它值。
手(shou)動狀態0.3m/s~1m/s,視窗的高低不影響面(mian)所設定風速;
3) 通(tong)(tong)風系統使用終端(duan)噪(zao)音≤55dB ,通(tong)(tong)風柜(ju)面換氣次數:不小于(yu)15次;
4) 主風(feng)(feng)管設計風(feng)(feng)速小(xiao)于(yu)9-12m/s,支風(feng)(feng)管設計風(feng)(feng)速小(xiao)于(yu)5-7m/s
5) 排風量:通風柜1500m3/h;
6) 快速執行器(qi)響應時間≤1s。
二、 開窗通風機系統符合要求1) VAV變(bian)風(feng)量變(bian)頻調節(jie)控(kong)制,保證系統多個通(tong)風(feng)柜(罩(zhao))同時運(yun)行時,各(ge)自獨(du)立調節(jie),不相互干擾(rao)。
2) 實驗室(shi)內(nei)氣(qi)流(liu)組織良好,氣(qi)流(liu)速度及紊(wen)流(liu)度均能控制在較小的范圍內(nei),以免室(shi)內(nei)氣(qi)體的擾動引起排毒柜(ju)內(nei)氣(qi)體外溢。
3) 應有不同(tong)型(xing)號和規格的圓形(xing)或矩形(xing)單個(ge)變風(feng)量閥,滿(man)足不同(tong)風(feng)量要求(qiu)并與設計(ji)圖紙相符合;
4) 結合實驗室(shi)(shi)排(pai)風控制系統(tong),包(bao)括變風量閥(fa)、消音器等能提(ti)供實驗室(shi)(shi)通(tong)風控制的完整解決方案(an)。
5) 實(shi)驗室風(feng)(feng)管(guan)在選擇防腐(fu)(fu)蝕較好,硬(ying)度高的(de)材(cai)質(zhi)。本(ben)工程涉及到所有風(feng)(feng)管(guan)均可采用防腐(fu)(fu)蝕性能(neng)好的(de)PVC/UPVC材(cai)質(zhi),風(feng)(feng)機(ji)全(quan)部為腐(fu)(fu)蝕性能(neng)好的(de)玻璃鋼風(feng)(feng)機(ji)。
6) 控制面板為漢字(zi)顯示(shi),可(ke)顯示(shi)通(tong)風系統運行時(shi)的多(duo)項信息。自動與手動多(duo)種工作模式可(ke)兼容設定,控制插座電(dian)源及照明的開(kai)啟,可(ke)調(diao)節風閥角(jiao)度(du)。
7) 實驗室(shi)內(nei)氣流組織良好(hao),送(song)回(hui)風氣流速度及紊流度均能控(kong)制在較小(xiao)的范(fan)圍內(nei),以免室(shi)內(nei)氣體的擾(rao)動引起排毒(du)柜內(nei)氣體外溢。